QualifiedMedium risk

SSR not switching on (load won't energise)

A solid-state relay won't turn its load on even when commanded — the heater/load stays off because the SSR isn't conducting.

Safety first

SSRs switch live power. Prove dead before working on the load side. Note SSRs can have small leakage even when off — don't treat the load as dead based on the control signal alone.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    No control signal to the SSR

    Most likely

    The control/trigger voltage isn't reaching the SSR input, so it never turns on.

  2. 2

    Control signal below threshold

    #2

    The input voltage is present but too low to reliably trigger the SSR.

  3. 3

    SSR failed open

    #3

    The SSR has failed in the non-conducting state and won't pass power.

  4. 4

    No load-side supply

    #4

    The power feeding the SSR's load side is missing, so nothing can flow even if it switches.

  5. 5

    Wrong SSR type (DC vs AC control / zero-cross)

    Least likely

    A mismatch between the control signal type and the SSR input prevents triggering.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Measure the control/trigger voltage at the SSR input when 'on' is commanded.

Expected reading

Control voltage present and within the SSR's input range.

If it passes

Control signal good — check the load-side supply and the SSR output.

If it fails

No/low control signal — trace the controller output and wiring.

View all expected readings at once
1. Measure the control/trigger voltage at the SSR input when 'on' is commanded.
Control voltage present and within the SSR's input range.
2. Confirm the load-side supply is present at the SSR.
Full supply on the SSR's load side.
3. Confirm the SSR input type matches the control signal (DC/AC, voltage range).
Control type matches the SSR input.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    SSR won't switch on

    → step 2
  2. 2
    decision

    Is a valid control signal present at the SSR input?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the load-side supply present?

    Yes→ step 5No→ step 6
  4. 4
    result

    No/low control signal — trace the controller output and wiring.

  5. 5
    decision

    Does the control type match the SSR input?

    Yes→ step 7No→ step 8
  6. 6
    result

    No load-side supply — restore it.

  7. 7
    result

    SSR failed open — replace it.

  8. 8
    result

    Type mismatch — fit the correct SSR.

Common mistakes apprentices make

  • Not checking the control signal actually reaches the SSR input.
  • A control voltage too low to trigger the SSR reliably.
  • Forgetting the SSR needs its load-side supply too.
  • Mismatching DC/AC control type to the SSR input.

When to stop & escalate

Repeated SSR failures point to heatsinking or rating problems to correct. Confirm the correct SSR type/rating for the control and load when replacing.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.