VSD powered and fault-free but won't accept the run command
The drive is powered, shows no fault, and the display looks normal — but it ignores the run command and the motor never turns. Often a 'not ready' / 'STO' / enable status, not a trip.
Safety first
Safe Torque Off (STO) and enable inputs are safety functions — they are there to stop the motor running. Never strap or defeat an STO/enable to 'make it go'. Work to the drive manual and the machine safety drawings.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Safe Torque Off / enable input not satisfied
Most likelyMost drives won't run unless the STO/enable terminals are made by the safety circuit (E-stop, guard, safety relay). If that circuit is open, the drive stays 'not ready' with no fault.
- 2
Run command not reaching the drive / wrong control source
#2The drive may be set to take its run command from a different source (terminals vs keypad vs network) than the one being used, so the command is ignored.
- 3
Missing run permissive / interlock
#3A process interlock (level, pressure, door, upstream ready signal) that must be made before run is missing, holding the drive off by design.
- 4
Drive in local/keypad mode or disabled
Least likelyThe drive left in local/hand or with a disable parameter set won't respond to the remote run command.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeRead the drive's status/ready indication and check whether STO/enable shows satisfied or open.
Drive shows ready with STO/enable made.
Safety enable is made — look at the run command source and permissives.
STO/enable not satisfied — trace the safety circuit (E-stop, guard, safety relay). Do NOT bypass it.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
VSD won't accept run, no fault
→ step 2 - 2decision
Is STO/enable satisfied (drive ready)?
Yes→ step 3No→ step 4 - 3decision
Does the control source match how run is commanded?
Yes→ step 5No→ step 6 - 4result
Safety enable open — trace the safety circuit (do not bypass).
- 5decision
Are all run permissives/interlocks made?
Yes→ step 7No→ step 8 - 6result
Wrong control source — set terminal/keypad/network to match.
- 7result
Recheck local/remote mode and any disable parameter.
- 8result
Missing permissive/interlock — satisfy the real condition, don't defeat it.
Common mistakes apprentices make
- Strapping out an STO/enable or interlock to force a run — defeating a safety function.
- Looking only for a fault code when the issue is a 'not ready' status.
- Sending a keypad command while the drive is set to terminal/network control.
- Missing a process permissive that must be made first.
When to stop & escalate
Any STO/enable/safety-circuit issue is a safety matter — escalate and resolve the safety circuit properly rather than bypassing it. If a permissive is missing due to an upstream process fault, hand off to the relevant system owner.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
VSD powered up but won't start the motor
The drive is energised and the display is alive, but it won't run the motor. No fault may be shown — it just sits in 'ready' or 'stopped' and ignores the start command.
E-stop circuit won't reset / machine won't start
The machine won't start because the emergency-stop circuit won't reset — the safety relay stays dropped out, holding everything off, even with all e-stops apparently released.
VSD/drive ignores the direction command
A drive runs but only one way — the reverse (or forward) command is ignored, even though the drive is running and the motor turns.