QualifiedMedium risk

Voltage drop on a long cable run

Equipment at the end of a long run misbehaves — dim lights, a contactor that won't hold, a motor struggling — because volt-drop along the cable leaves too little voltage at the load.

Safety first

Measure under load to see real volt-drop. Treat the circuit as live while testing and isolate before any wiring work.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Cable too small / run too long for the load

    Most likely

    Conductor size and length mean significant volt-drop under load, starving the far end.

  2. 2

    High-resistance joint along the run

    #2

    A loose or corroded joint adds resistance and drops voltage, often with local heating.

  3. 3

    Overloaded circuit

    #3

    More load than designed increases the current and the volt-drop.

  4. 4

    Loose terminations at either end

    Least likely

    Loose terminals at the supply or load end create extra drop.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Measure voltage at the supply end and at the load end, under load, and compare.

Expected reading

Only a small difference between the two under load.

If it passes

Little drop — the load problem is elsewhere, not volt-drop.

If it fails

Significant drop under load — quantify it and find where it occurs.

View all expected readings at once
1. Measure voltage at the supply end and at the load end, under load, and compare.
Only a small difference between the two under load.
2. Measure along the run (or at intermediate joints) to see whether the drop is gradual (cable) or at a point (joint).
Either a gradual drop (cable/length) or a step at a bad joint.
3. Check terminations at both ends and the actual load current against the cable's capability.
Tight terminations and load within the cable's design.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Volt-drop on long run

    → step 2
  2. 2
    decision

    Is there significant drop end-to-end under load?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the drop a step at a joint (vs gradual)?

    Yes→ step 5No→ step 6
  4. 4
    result

    Little drop — the issue isn't volt-drop; look elsewhere.

  5. 5
    result

    Bad joint — repair the high-resistance connection.

  6. 6
    decision

    Are terminations tight and load within cable capability?

    Yes→ step 7No→ step 8
  7. 7
    result

    Run undersized for the duty — design change needed.

  8. 8
    result

    Loose termination or overload — repair/rebalance.

Common mistakes apprentices make

  • Measuring with no load and seeing no drop.
  • Not localising whether the drop is gradual or at a joint.
  • Overlooking a high-resistance joint that also runs hot.
  • Ignoring that the circuit is simply overloaded.

When to stop & escalate

If the cable is genuinely undersized for the run/duty, the remedy is a design change (larger conductor or reduced load) — plan it rather than working around it. A hot joint should be repaired promptly.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.