QualifiedHigh risk

Mains (hardwired) smoke alarm not working / no light

A hardwired smoke alarm's power indicator is off or it isn't functioning — points at the alarm's supply (often a lighting circuit), the alarm itself, or end of life.

Safety first

Smoke alarms are life-safety devices — don't leave one out of service. Isolate before working; mains alarms are licensed electrical work.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Supply to the alarm lost

    Most likely

    The alarm's supply (often shared with a lighting circuit) is off or tripped.

  2. 2

    End-of-life / faulty alarm

    #2

    The alarm has expired or failed and must be replaced.

  3. 3

    Loose connection at the alarm base

    #3

    A loose connection in the alarm's base plug/terminals.

  4. 4

    Backup battery depleted (on a faulted unit)

    Least likely

    On a unit that's lost mains, a depleted backup leaves it fully dead.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 2
1

Confirm the alarm's supply circuit is live (and not tripped); check the alarm's power indicator.

Expected reading

Supply present; indicator should be on.

If it passes

Powered but not working — suspect the alarm (end of life/fault).

If it fails

No supply / tripped — restore (find why if tripped).

Mark this test
View all expected readings at once
1. Confirm the alarm's supply circuit is live (and not tripped); check the alarm's power indicator.
Supply present; indicator should be on.
2. Isolate and check the alarm base connections, and the alarm's age/condition.
Sound connections; alarm within service life.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Mains alarm not working

    → step 2
  2. 2
    decision

    Is the alarm's supply circuit live (not tripped)?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Are the base connections sound and the alarm within life?

    Yes→ step 5No→ step 6
  4. 4
    result

    Restore the supply circuit (find why if tripped).

  5. 5
    result

    Powered but dead — replace the alarm.

  6. 6
    result

    Loose connection or end-of-life — rectify/replace.

Common mistakes apprentices make

  • Leaving a mains alarm out of service.
  • Not realising it shares a circuit with lighting (check that circuit).
  • Overlooking a loose base connection.
  • Keeping an expired alarm.

When to stop & escalate

Mains smoke alarm replacement and wiring is licensed electrical work and must keep the alarm in service. Replace expired/faulty units promptly.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults