Analogue sensor (4-20mA / 0-10V) reading wrong
An analogue sensor (pressure, level, temperature) gives a wrong or fixed reading — stuck at zero, pinned at full scale, or simply not matching reality.
Safety first
Wrong analogue readings can drive a process to act incorrectly. Treat readings as suspect until verified. Isolate before working on wiring.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
Premium fault tree
The full ranked causes, test sequence and flowchart for this fault are part of Sparkie Sidekick Pro.
Coming soon — no payment required during preview.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Full test sequence
The step-by-step test flow with expected readings for this fault is part of Sparkie Sidekick Pro.
Coming soon — no payment required during preview.
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Analogue reading wrong
→ step 2 - 2decision
Does the measured signal match the real process value?
Yes→ step 3No→ step 4 - 3decision
Does the controller scaling match the sensor range?
Yes→ step 5No→ step 6 - 4decision
Does a known injected signal read correctly at the input?
Yes→ step 7No→ step 8 - 5result
Signal and scaling fine — check/redo calibration.
- 6result
Scaling mismatch — correct the range/units in the controller.
- 7result
Input fine — sensor/transmitter or wiring at fault; calibrate/replace.
- 8result
Input channel fault — controller maintenance.
Common mistakes apprentices make
- Trusting the displayed value without measuring the actual signal.
- Mismatched scaling between sensor range and controller config.
- Forgetting loop power on a 4-20mA transmitter.
- Replacing the sensor when it just needs recalibration or rescaling.
When to stop & escalate
Calibration against a reference should follow your procedure/standards. A failed analogue input channel means controller maintenance per site procedure (with backups).
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
Sensor intermittent / drops out randomly
A sensor works most of the time but drops out or false-triggers intermittently, causing random stops, miscounts, or sequence faults that are hard to pin down.
Encoder feedback fault (position/speed wrong)
Position or speed feedback from an encoder is wrong — counts drift, position is lost, or a drive faults on encoder loss, so motion control misbehaves.
PLC input not reading despite a signal present
A field device is clearly providing a signal, but the PLC input bit/LED doesn't come on — the program never sees the input, so logic that depends on it won't run.